RackLink™ Power Management System
Practical Power Management for AV Installations


RackLink
Introducing the RackLink™ Power Management System from Middle Atlantic Products – a practical web-enabled power management system that sets a new standard for A/V installations. Set it up in less than 5 minutes and it will monitor the power and temperature conditions of your system, log and alert you to any irregularities, and even reboot or take another action to correct problems on its own. We’ve made it easy to set up and operate, with an open architecture that integrates seamlessly with leading control systems – even your smart phone – and is compatible with 'cloud' based services but is not dependent on them.
Remotely managed power products that provide integrators with real-time visibility and control over any installation from anywhere in the world.
All RackLink™ series products are fully compliant with any control system or content aggregator. Drivers available now from select control system partners.

AC Power
Connection Type Rackmount models: 9ft SignalSAFE Cord (15A / 20A) In-Line Models: 3ft SignalSAFE IEC (15A / 20A)
Line Voltage Nominal: 120 VAC Minimum: 80 VAC / Maximum:140 VAC
Maximum Peak load 15A models: 15 Amps 20A models: 20 Amps
Maximum Continuous Load 15A models: 12 Amps 20A models: 16 Amps

Alert Threshold Range
Input Voltage Alert Low: 105 VAC - 110 VAC High: 123 VAC - 128 VAC
Load Current Alert Minimum: 0A Maximum: 15A / 20A (15A models / 20A models)
Temperature Alert Min: 0 deg F Max: 140 deg F

Surge Specification
Peak Impulse Current (8/20 micro seconds)
  • 30,000 Amps, one time
  • 19,500 Amps, two times within 5 minutes
  • 7,000 Amps, ten times within 2 minutes
  • Maximum peak impulse current pulse as defined between line and neutral
  • Maximum multiple impulse current derated per spec
Protection Mode Line to Neutral
Response time Less than 1 nanosecond
Surge energy dissipation 711 Joules (10 / 100 micro seconds)
EMI / RF Supression 20dB Calculated Line to Neutral - 100kHz to 1Mhz - based on nominal impedance
Event Driven/Responses
AutoPing No Response/Recovery Email and/or Control Outlet and/or Dry Contact
Over / Under Temperature Email and/or Control Outlet and/or Dry Contact
Over / Under Input Voltage Email
Over / Under Load Current Email
Communication RS-232
TCP/IP
HTTP (integrated web server)
Dimensions Rackmount models:
1.75" H x 19.25" W x 9" D

In-line models:
6" x 3" x 2.5" (can be mounted in any orientation)
Warranty All models:
3 years limited warranty


Customer Portal Consultant Zone Middle Atlantic Products Tech Docs Tech Docs Spec Clips™ Tech Docs